HomeOur ServicesOutdoor Dry Type JLSZV/Y-6, 10, 35

Outdoor Dry Type JLSZV/Y-6, 10, 35

Outdoor Dry Type JLSZV/Y-6, 10, 35
(1) JLSZV/Y-6, 10, 35 series combined transformers are assembled from dry-type units, and there is no oil leakage problem, so oil-free is achieved.
(2) Voltage and current are cast with imported resin, like a building block structure, easy to replace, easy to maintain, and save costs.
(3) The product has high accuracy, and the current transformer can reach 0.2S level, realizing wide load measurement.
(4) The use of special materials makes the product have high dynamic and thermal stability.
(5) The voltage part can have a 220V auxiliary winding to provide power for switches, etc.

Main technical parameters of voltage part

Product Model

Rated primary voltage(V)

Maximum voltage of the device (V)

Rated secondary voltage (RV)

Accuracy level and output capacity
C O S φ = 0 . 8 ( hysteresis ) ( V A )

Maximum output capacity(V)

0.2

0.5

JLSZV-6

6

7.2

100

20

30

320

JLSZV-10

10

12

100

20

30

640

JLSZV-35

35

40.5

10

30

30

850

Main technical parameters of current part

Rated primary current (A)

Rated secondary current (A)

1s short-time thermal current (kA)

Rated dynamic stability current (kA)

     Accuracy level and output capacity

COSφ=0.8(hysteresis)(VA)

0.2S

0.2

0.5S

2.5;3;5;7.5;10;15;
20;25;30;40;50;60;
75;100;150;200;300;
   400;500;600;800;

5

75×1n

187.5×1n

10

10

10

1.25~2.5;2.5~5;5~10;
7.5~15;10~20;15~30;
20~40;25~50;40~80;
  50~75;50~100;75~
 150;100~200;150~300

5

75×1n

187.5×1n

10

10

10

Note: Dual current ratio specification: The secondary current of the dual ratio is indicated. The current ratio is 1SI, 1S2, 1S3; 2S1

2S2, 2S3; among which 1S1, 1S2; 2S1, 2S2 is a small current ratio; 1S1, 1S3; 2S1, 2S3 is a large current ratio.
The current ratio connection method should be selected according to the corresponding maximum capacity of the transformer.

Voltage transformer error limit table

Accuracy level

Rated voltage percentage %

Ratio Difference

Phase angle difference (minutes)

Secondary load (VA)

0.5

80、100、120

±0.5

±20

5~20

10~40

0.2

80、100、121

±0.2

±10

5~20

10~40

Current transformer error limit table

Accuracy level

Rated current percentage Ratio difference (%)

Rated current percentage Phase difference (min)

5

20

100~120

5

20

100~120

0.5S

1.50

0.75

0.5

90

45

30

0.2S

0.75

0.35

0.2

30

15

10

Error limit table of special current transformers

Accuracy level

Current error (±%)

Phase difference, at the following rated current (%)

At the following rated current (%)

±(’)

±card

 

5

20

100

120

1

5

20

100

120

 

5

20

100

120

0.5S

1.50

0.75

0.5

0.5

0.5

90

45

30

30

30

2.7

1.35

0.9

0.9

0.9

0.2S

0.75

0.35

0.2

0.2

0.2

30

15

10

10

10

0.9

0.45

0.3

0.3

0.3

Note: This table is only used for transformers with a rated secondary current of 5A

Transformer temperature rise limit

Transformer part

Temperature rise (°C)

Measuring direction

 

 

Coil

55

Resistance method

 

 

Coil outlet or contact connection

50

Thermometer method

 

×